Operation
The LD Series Fluid Controls operate by detecting the electrical
resistance of fluids. A sensitivity adjustment is provided to compensate for different
resistance levels, allowing the LD controls to sense most conductive fluids. (City Water,
Sea Water, Water and Glycol, Water and Oil, Coffee, Wet Soil, Weak Acid, Copper Sulphate,
Beverages)
A mode switch selects operation either as an upper or lower level control or as
a single level detector. A splash delay is also built in to override splashing in a tank.
Specifications |
| Operating Voltage |
24 VAC, 115 VAC or 240 VAC |
| Maximum Supply Variation |
+/- 10% |
| Output Contact Rating |
SPDT 15 Amp Non-inductive (rated
1/2 hp 125 VAC) |
| Ambient Operating Temperature |
-29° C to 71° C |
| Output Contact Type |
SPDT Form C |
| Power Consumption |
3 Watts |
| Probe Sensing Distance |
Up to 50 feet |
| Maximum Probe Current |
1 mA |
| Maximum Probe Voltage |
6 VAC |
| Resistance Detection Range |
up to 1 Meg ohm |
| Splash Delay Adjustment Range |
100 ms to 5 sec. |
| Probe Sensitivity Adjustment
Range |
8k to 1 Meg ohm |
| Termination Connection |
Barrier type strip up to 12 AWG |
| Mounting Type |
6-32 threaded standoffs |
| Probe Type |
RBE DP-1000 or equivalent |
| Operating Modes |
Upper/Lower level control or
single unit level control |
See connection diagram for description on control action
for single level or dual level control.
For Application Assistance,
Quotation, Product Specifications, or Custom Design Call 1-800-541-4056 |

Home | Up